The EvacU Elite Multi-Purpose Interface Card (MIC) provides 8 supervised inputs, two relay outputs, and a high-level interface to Ampac's FireFinder PLUS Fire Alarm Control Panel Add On Bus.
The EvacU Elite Multi-Purpose Interface Card occupies one slot in the EvacU Elite Universal Rack Frame.
Differential Input with Fault Feedback | 1 available, with 10kΩ EOL monitoring, floating reference (max 30VDC) with fault feedback (user selectable resistance) |
Differential Inputs | 3 available, with 10kΩ EOL monitoring, individual floating reference (max 30VDC) |
Single-Ended Inputs | 4 available, with 10kΩ EOL monitoring, common floating reference (max 30VDC) |
Relay Outputs (VFC) | 2 available, max voltage 48VDC / 30VAC, mx current 1A @ 30VDC, 0.5A @ 30VAC |
No. of Rack Slots Required | 1 |
Current Consumption | 44mA @24V DC (quiescent) |
6350-MIC | Multi-Purpose Interface Card |