TITANUS MICRO•SENS® air sampling smoke detection system was developed as a cost-effective solution for monitoring small to medium-sized spaces and equipment.
With the optional ROOM IDENT, this device makes use of patented technology that enables it to monitor up to 5 rooms or facilities and to identify the source of the alarm.
TITANUS MICRO•SENS® is available in a cold storage option, with a redundant fan, or as a detector box. The detector box option does not have its own fan and can be used in combination with TITANUS® systems to localise the sampling hole where the smoke is entering.
TITANUS MICRO•SENS® air sampling smoke detection system can be used to replace up to 8 point-type smoke detectors. This requires up to 50m of pipe, regardless of whether Class A, B or C is required in accordance with AS7240.20.
Approvals: AS 7240.20-2012
Number of Sensor Modules Fitted | 1 |
Max. Number of Sampling Holes | 8 |
Max. Total Pipe Length Capable | 50m |
Weight | 850 to 895g – depends on configuration |
Current – Start Up Maximum: | 150mA |
Current - Quiescent (at 24 VDC) | 105mA |
Current - Alarm (at 24 VDC) | 110-140mA (9V ventilator voltage) |
Operating Voltage | 24 VDC (14 - 30 VDC) |
Tapered Pipe Connectors | 2 x 25mm |
Detector Dimensions | 144mm W x 222mm H x 70mm D |
Housing Colour | RAL 9018, Papyrus White |
Cabinet Type, Rating | ABS Plastic, IP20 (IP54 with air return) |
Temperature - Standard Version | -20 °C to + 60 °C |
Temperature - Freezer Version | -40 °C to + 60 °C |
Humidity (Permanent) | 10-95% Rel. Non-Condensing |
Cable Entries | 8 x M20, 2 x M25 |
Sensor Head Sensitivities | 0.5% and 0.1% |
Interface Types | Relays |
Alarms | 2 Adjustable Alarm Threshold |
Fault Signals |
|
Clamped Connections | Max. 1.0 mm² |
Front Panel Control & Indications | Operational: Green; Fire Alarm: Red; Action Alarm: Red (optional); Fault: Yellow; Smoke Level: 10 x Yellow Bar Graph (optional); Alarm Location: 5 x Red (optional) |
Noise Level | Standard & Freezer - 40 dB(A). Reduction by 10dB(A) possible by using the noise suppressor (AD-10-0005) |
Event Log | Inbuilt, access thru Diag Tool |
Redundant Fan | Optional |
7010-6001/6002 | MicroSens 0.5% / 0.1% |
7010-6011/6012 | MicroSens 0.5% / 0.1% Bar Graph |
7010-6100/6101 | MicroSens 0.5% / 0.1% Freezer |
7010-6110/6111 | MicroSens 0.5% / 0.1% Freezer and Bar Graph |
7010-6301/6302 | MicroSens 0.5% / 0.1% Room Ident |
7010-6311/6312 | MicroSens 0.5% / 0.1% Bar Graph and Room Ident |