The Apartment Module (AM) is a loop-powered addressable device that helps reduce the costly consequences of an unwanted alarm.
An occupant is able to silence a local audible warning, activated by a local smoke detector, and allowing a preset time to investigate the cause of the alarm. Local smoke detectors can be connected directly to the AM (conventional) or connected to the addressable loop (addressable) and assigned to the AM.
Operating Voltage | 21 to 28 VDC (loop powered) |
Quiescent Current | 4.9mA with 6k2Ω EOL / 1.9mA with 10µF EOL |
Alarm Current | 4.2mA + Zone alarm current of 14.5mA |
Zone Circuit | 10 detectors (max) with 6k2Ω EOL (detector current < 1.2mA) or 20 detectors (max) with 10µF EOL (detector current < 2.4mA) |
Zone EOL | 6k2Ω, 100µF |
Speaker Circuit | 100Volt line, 6 W max, 47k EOL |
Address Setting | 1 to 126 |
Dimension | Single Gang PDL Plate |
Material | High Impact ABS (white) |
Weight | 45 grams |
226-0003 | Apartment Module (Vertical) |
226-0005 | Apartment Module (Horizontal) NB: By Special Order |