The Addressable Air Duct Sampling Unit provides early detection of smoke in the air moving through heating and ventilation (HVAC) ducts in commercial and industrial premises. It has been designed to monitor levels of smoke in air ducts operating at airspeeds of 0.5 to 20 meters per second.
The unit can be fitted to any wall of a ventilation duct and has two tubes that extend into the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector, and exhausted back into the air duct.
Approvals: AS 1603.13:2018
Housing | Grey - ABS |
Cover | Transparent - ABS |
Operating Voltage | 9-33 V DC |
Dimension | H 115mm x W 340mm x D 60mm |
Temperature Range | 0°C to +60°C |
Humidity | Up to 85% (no condensation) |
Weight | 5.5 kg |
214-0051 | Duct Sampling Unit inc XP95 Detector Base |
214-0060 | Duct Probe 300mm to 750mm Sampling Pipe |
214-0061 | Duct Probe 750mm to 1500mm Sampling Pipe |
214-0062 | Duct Probe 1500mm to 3000mm Sampling Pipe |
201-0003 | XP95 Optical Smoke Detector |
201-0094 | Discovery Multisensor Detector |