The Soteria Twin Switch Monitor Unit provides the function of two Switch Monitor units within one enclosure. The two units are electrically independent of each other. There is a DIL switch on each unit to set the address.
Both Switch Monitor units in the enclosure are designed to monitor the state of one or more single-pole, volt-free contacts connected on a single pair of cables to report the status. It has a selectable status reporting delay making it suitable for monitoring flow switches.
Approvals: AS ISO 7240.18:2015
Supply Voltage (Vmin—Vmax) | 17 to 35V dc |
Protocol | 5-13V peak to peak |
Power-Up Surge Current | 900µA per Switch Monitor |
Quiescent Current | 500µA per Switch Monitor |
Max Current LEDs On | 2mA per Switch Monitor |
Max Current LEDs Disabled | 500µA per Switch Monitor |
Isolator Data | Refer to short-circuit isolation datasheet PDS201-9001 |
Operating Temperature | -40°C + 70°C |
Humidity | 0% to 95% RH (no condensation or icing) |
Vibration, Impact, and Shock | EN54-17, EN54-18, AS7240.17 & AS7240.18 |
Standards & Approvals | EN54-17, EN54-18, CPR, LPCB, AS7240.17, AS7240.18 & SAI Global |
Dimensions | 60mm H x 150mm W x 90mm D |
Weight | 273 grams |
4110-1106 | Soteria Twin Switch Monitor Unit |